Ethernet-APL

Ethernet-APL is a two-wire Ethernet physical layer for process automation and hazardous locations, based on 10BASE-T1L. It provides 10 Mbit/s full-duplex communication and power over cable runs up to 1000 m using trunk-and-spur topology with point-to-point segments. It is intended to carry higher-level Ethernet protocols such as PROFINET and OPC UA.

Source checked3/3 values · 2026-10-25

Specification

2 sources
Transportsethernet l2
Architectureclient server
Encodingbinary
Standard bodyIEEE and IEC
Standard refIEC TS 60079-47; 10BASE-T1L

Study notes

  • Based on IEEE and IEC standards; uses 10BASE-T1L single-pair Ethernet.
  • Specifies point-to-point connections only, with each connection between communications partners forming a segment.
  • Uses a switched architecture and a trunk-and-spur topology.
  • Trunk cable lengths can reach 1000 m; spur lengths can reach 200 m with optional intrinsic safety.
  • Can power up to 50 field devices with up to 500 mW each.
  • Defines two switch types: a power switch that feeds power and communication into trunk ports, and a field switch that provides at least one spur port and can be powered via the trunk or externally.
  • Defines port profiles for multiple power levels with and without hazardous area protection.
  • Reuses existing fieldbus cable type A and uses FISCO installation practices.
  • Requires conformance testing for devices and components.
  • The APL Project was established in 2018 and backed by FieldComm Group, ODVA, OPC Foundation, and PROFIBUS & PROFINET International.

Safety

  • Designed for hazardous locations and supports all explosion protection techniques including intrinsic safety.
  • IEC TS 60079-47 (2-WISE) defines intrinsic safety protection for all hazardous Zones and Divisions and provides simple verification steps without complex calculations.
  • Ethernet-APL port profiles cover multiple power levels with and without hazardous area protection.
  • Spur segments carry lower power and can have optional intrinsic safety for lengths up to 200 m.
  • PROFINET over APL devices are certified under the same criteria as other PROFINET devices.