AutomationDirect GS4-4250

The GS4-4250 is a DURApulse GS4 series AC variable frequency drive in an open-frame, wall-mount housing. It takes 460 VAC three-phase input and is rated 250 hp with 3-phase input, using either sensorless vector control (SVC) or V/Hz control to drive three-phase induction motors. It provides RS-485 communications, analog and discrete I/O, and an embedded ladder-logic PLC function.

Source checked10/10 values · 2026-10-26AutomationDirectVFD
Rated current
352A
Weight
171kg

Specification

2 sources
Categoryvfd
Supply voltage460 VAC
Frame sizeG
Output typePWM output
Operating temp min-10 °C
Operating temp max50 °C

Quick answers

How much does the AutomationDirect GS4-4250 weigh?
171 kg, per DURApulse AC High-performance Drive: 460 VAC, 250hp with 3-phase input, (VFD) (PN# GS4-4250) | AutomationDirect (automationdirect.com).

Study notes

  • DURApulse GS4 series, G frame size, controller type listed as high-performance.
  • Control modes: SVC or V/Hz; output type PWM; reverse capability built-in.
  • Carrier frequency range 2-15 kHz; output frequency range 0.1-599 Hz.
  • Current ratings: 352 A amperage rating, 370 A variable torque rating.
  • Serial port: one RS-485 (RJ12) connection supporting Modbus RTU, Modbus ASCII and BACnet at up to 115.2k baud.
  • I/O: 8 discrete inputs at 24 VDC (sinking/sourcing), 4 discrete outputs (relay/sinking/sourcing, 240 VAC and 48 VDC), 2 Form C (SPDT) relays.
  • Analog I/O: 3 inputs (0-20 mA / 4-20 mA, +/-10 VDC, 11-bit) and 2 outputs (0-20 mA / 4-20 mA, 0-10 VDC, 10-bit).
  • Load current 3 A/point for relays and 50 mA/point for discrete outputs; screw terminal connectors.
  • Programming language: ladder logic (GSLOGIC drive PLC software, GSOFT2 configuration software).
  • Optional EtherNet/IP and Modbus TCP communication cards are available; an EDS file and Rockwell AOI are provided.
  • Enclosure is open frame with IP00 and IP20 ratings; no integrated EMI filter; not internally bypassed.
  • Shipping weight 377 lb (about 171 kg); country of origin Taiwan.

Safety

  • Safe Torque Off (STO) is built-in.
  • Open-frame enclosure, IP00 and IP20, wall mounting; must be installed in an appropriate enclosure environment.
  • An external dynamic braking unit is required.
  • A user-supplied external fuse is required.
  • Operating temperature rating -10 to +50 deg C.