MODBUS RTU

MODBUS RTU is the binary serial-line transmission mode of the MODBUS master-slave protocol. A master sends a request frame containing slave address, function code, data, and CRC; only the addressed slave replies. RTU is the default and mandatory mode for MODBUS over serial line, using silent intervals to delimit frames.

Source checked15/15 values · 2026-10-25

Specification

2 sources
Transportsserial
Architecturemaster slave
Encodingbinary
Standard bodyModbus.org

Data types

NameSize (bits)Description
Coils1Single-bit read-write data type
Discrete Inputs1Single-bit read-only data type
Input Registers1616-bit word read-only data type
Holding Registers1616-bit word read-write data type

Study notes

  • RTU mode is mandatory for MODBUS serial-line devices; ASCII mode is optional, and the default setup must be RTU.
  • RTU frame fields are slave address (1 byte), function code (1 byte), data (0 up to 252 bytes), and CRC (2 bytes); maximum RTU frame size is 256 bytes.
  • RTU character format is 8 data bits LSB first, 1 start bit, 1 parity bit, and 1 stop bit; no parity requires 2 stop bits. Default parity is even.
  • Message frames are separated by at least 3.5 character times (t3.5); a silent interval greater than 1.5 character times between characters makes the frame incomplete and it should be discarded.
  • For baud rates above 19200 bps, recommended fixed timer values are 750 microseconds for t1.5 and 1.750 milliseconds for t3.5.
  • CRC-16 uses polynomial 0xA001 and initial register value 0xFFFF; the low-order CRC byte is transmitted first, followed by the high-order byte.
  • The master initiates only one transaction at a time; slave nodes never transmit without a request and never communicate with each other.
  • Unicast transactions use a slave address from 1 to 247; broadcast uses address 0, is write-only, and returns no response.
  • Typical turnaround delay after a broadcast is 100 ms to 200 ms; response timeout is application-dependent and is typically 1 s to several seconds at 9600 bps.
  • The MODBUS data model defines coils and discrete inputs as single-bit objects and input registers and holding registers as 16-bit words.
  • 9600 bps and 19.2 Kbps are required data signaling rates; 19.2 Kbps is the required default. Optional rates include 1200, 2400, 4800, 38400, 56 Kbps, and 115 Kbps.

Safety

  • If a slave detects a transmission error in a received frame, it does not act on the message and does not construct a response; the master's response timeout then expires.
  • Connection of a crossed cable in a 2-wire MODBUS system may cause damages.
  • Ensure at device addressing time that no two devices share the same address; duplicate addresses can cause abnormal behavior of the whole serial bus and prevent the master from communicating with all slaves.
  • The Common circuit must be connected directly to protective ground, preferably at one point only for the entire bus.
  • A MODBUS over Serial Line cable must be shielded, and at one end of each cable its shield must be connected to protective ground.
  • Line termination is required near each of the two ends of the bus; never place line termination on a derivation cable, and do not place more than two line terminations on one passive D0-D1 balanced pair.
  • RS232-MODBUS should only be used for short point-to-point interconnection, typically less than 20 m.
  • A figure of 32 devices is always authorized on any RS485-MODBUS system without repeater; line polarization reduces the maximum number of devices by 4.
  • For a maximum 9600 baud rate and AWG26 or wider gauge, the maximum trunk length is 1000 m; in the specific case of 4-wire cabling used as a 2-wire system, the maximum length must be divided by two.