AutomationDirect DURApulse GS33-2040

The GS33-2040 is a DURApulse GS30 series enclosed AC variable frequency drive rated 40 hp with three-phase 230 VAC input and output. It controls three-phase induction and permanent magnet AC motors using SVC, V/Hz, FOC, encoder or torque control modes. It has an RS-485 (RJ45) port and a USB B port, with Modbus RTU or Modbus ASCII slave communication, and requires an external dynamic braking unit.

Source checked12/12 values · 2026-10-26AutomationDirectVFD
Rated power
29.828kW
Rated current
120A
IP rating
IP20
Weight
38.1018kg

Specification

2 sources
Categoryvfd
Supply voltage230 VAC
Frame sizeI
Output typePWM output
Operating temp min-20 °C
Operating temp max50 °C

Quick answers

How much does the AutomationDirect DURApulse GS33-2040 weigh?
38.1018 kg, per DURApulse AC High-performance Drive: 230 VAC, 40hp with 3-phase input, (VFD) (PN# GS33-2040) | AutomationDirect (automationdirect.com).
What is the IP rating of the AutomationDirect DURApulse GS33-2040?
IP20, per DURApulse AC High-performance Drive: 230 VAC, 40hp with 3-phase input, (VFD) (PN# GS33-2040) | AutomationDirect (automationdirect.com).

Study notes

  • Series: GS30; controller type: high-performance; frame size I.
  • Input and output voltage 230 VAC, three input phases and three output phases.
  • Amperage rating 120 A; variable torque amperage rating 134 A.
  • Control modes: SVC, V/Hz, FOC, encoder or torque.
  • Carrier frequency range 2-15 kHz; output frequency range 0.1-599 Hz.
  • Communication: (1) RS-485 (RJ45) and (1) USB B; port speed up to 115.2k baud; Modbus RTU Slave and Modbus ASCII Slave.
  • Discrete I/O: 7 sinking/sourcing inputs at 24 VDC and 3 relay/sinking/sourcing outputs rated 240 VAC and 30 VDC; one Form C (SPDT) relay; load current 3 A/point relay, 50 mA/point discrete.
  • Analog I/O: 2 input channels (0-20 mA, 4-20 mA, +/-10 VDC, 12-bit) and 1 output channel (0-20 mA, 4-20 mA, 0-10 VDC, 10-bit).
  • Input signal options: 4-20 mA, voltage, potentiometer or pulse train; output type PWM.
  • Reverse capability built-in; integrated EMI filter: no; internally bypassed: no.
  • Programming language: ladder; connector type: spring clamp terminals.
  • Optional communication, encoder and I/O modules are available.

Safety

  • Safe Torque Off (STO) is built-in.
  • An external dynamic braking unit is required.
  • Fuse type: user-supplied external fuse.
  • Temperature rating -20 to +50 deg C.
  • Enclosure type enclosed, IP20; mounting panel or wall.
  • UL Listed File # E198015; CE declaration available; RoHS status yes.