AutomationDirect GS31-22P0

The GS31-22P0 is an enclosed DURApulse GS30 series AC variable frequency drive rated for 230 VAC single-phase input and 3-phase output, 2 hp with 1-phase input. It controls 3-phase induction and permanent magnet AC motors using SVC, V/Hz, FOC, encoder or torque control modes. It provides an RS-485 (RJ45) port and a USB B port, integrated dynamic braking, and connections for optional communication, encoder and I/O modules.

Source checked10/10 values · 2026-10-26AutomationDirectVFD
Rated current
7.5A
IP rating
IP20

Specification

2 sources
Categoryvfd
Supply voltage230 VAC
Frame sizeC1
Output typePWM output
Operating temp min-20 °C
Operating temp max50 °C

Quick answers

What is the IP rating of the AutomationDirect GS31-22P0?
IP20, per DURApulse AC High-performance Drive: 230 VAC, 2hp with 1-phase input, (VFD) (PN# GS31-22P0) | AutomationDirect (automationdirect.com).

Study notes

  • Rated 2 hp with 1-phase input; amperage rating 7.5 A, variable torque amperage rating 8.5 A.
  • Control modes: SVC, V/Hz, FOC, encoder or torque.
  • Carrier frequency range 2-15 kHz; output frequency range 0.1-599 Hz.
  • Analog inputs: 2 channels, current/voltage, 12-bit, 0-20 mA and 4-20 mA or +/-10 VDC.
  • Analog output: 1 channel, 10-bit, 0-20 mA and 4-20 mA or 0-10 VDC.
  • Discrete inputs: 7 points at 24 VDC, sinking/sourcing, in 2 non-isolated commons of 4 points.
  • Discrete outputs: 3 points (240 VAC and 30 VDC), relay/sinking/sourcing, one Form C (SPDT) relay, 3 A/point relay and 50 mA/point discrete.
  • Communication: (1) RS-485 (RJ45) and (1) USB B; port speed up to 115.2k baud; Modbus RTU Slave and Modbus ASCII Slave protocols.
  • Programming language ladder; spring clamp terminals; mounting on 35 mm DIN rail, panel or wall.
  • Input signal options: 4-20 mA, voltage, potentiometer or pulse train; output type PWM.
  • No integrated EMI filter; not internally bypassed.
  • Item shipping weight 3.55 lb; country of origin India.

Safety

  • Safe Torque Off (STO) is built-in.
  • UL Listed File # E198015; CE declaration and RoHS status Yes; no UL Recognized, UL Hazardous or CSA file.
  • A user-supplied external fuse is required.
  • Operating temperature rating -20 to +50 deg C.
  • IP20 enclosure rating.