AutomationDirect GS23-55P0

The GS23-55P0 is an enclosed general-purpose AC variable frequency drive from the DURApulse GS20 series. It accepts 575 VAC three-phase input and runs three-phase induction or permanent magnet AC motors at 5 hp, using SVC, V/Hz, FOC or torque control modes. It has a built-in keypad, integrated dynamic braking, spring clamp terminals and an RS-485 port for Modbus RTU or ASCII slave communication.

Source checked10/10 values · 2026-10-26AutomationDirectVFD
Rated current
6.6A
IP rating
IP20

Specification

2 sources
Categoryvfd
Supply voltage575 VAC, 3-phase
Frame sizeC
Output typePWM output
Operating temp min-20 °C
Operating temp max50 °C

Quick answers

What is the IP rating of the AutomationDirect GS23-55P0?
IP20, per DURApulse AC General Purpose Drive: 575 VAC, 5hp with 3-phase input, (VFD) (PN# GS23-55P0) | AutomationDirect (automationdirect.com).

Study notes

  • Control modes are SVC, V/Hz, FOC or torque; output frequency range is 0.1-599 Hz and carrier frequency range is 2-15 kHz.
  • I/O: 7 discrete inputs (24 VDC, sinking/sourcing) and 3 discrete outputs (relay/sinking/sourcing), with one Form C (SPDT) relay.
  • Analog: 2 input channels (0-20 mA, 4-20 mA, +/-10 VDC; 10-bit and 12-bit) and 1 output channel (0-20 mA, 4-20 mA, 0-10 VDC; 10-bit).
  • Communication ports are one RS-485 (RJ45) and one USB B, with port speeds up to 115.2k baud.
  • Input signal options are 4-20 mA, voltage, potentiometer or pulse train input; drive output is PWM.
  • Programming language is ladder; connector type is spring clamp terminals; mounting is panel or wall.
  • An optional EtherNet/IP and Modbus TCP card is available but is not a native port on this part number.
  • Rated 6.6 A, with a variable torque rating of 8 A; reverse capability is built-in and the drive is not internally bypassed.
  • No integrated EMI filter; an integrate dynamic braking circuit is included.
  • UL Listed File # E198015; RoHS status Yes.

Safety

  • Safe Torque Off (STO) is built-in.
  • Enclosure rating is IP20.
  • Operating temperature rating is -20 to +50 deg C.
  • A user-supplied external fuse is required.
  • The drive is intended for 3-phase induction and permanent magnet AC motors.
↑↓ navigate↵ openesc close