AutomationDirect DURApulse GS11N-21P0

The GS11N-21P0 is an enclosed DURApulse GS10 series AC micro variable frequency drive. It takes single-phase 230 VAC input and produces three-phase 230 VAC output for 3-phase induction and permanent magnet AC motors, rated 1 hp with 1-phase input. It runs in SVC or V/Hz control mode and provides an RS-485 port for Modbus RTU/ASCII slave communication plus integrated dynamic braking.

Source checked11/11 values · 2026-10-26AutomationDirectVFD
Rated power
0.746kW
Rated current
4.8A
IP rating
IP20

Specification

2 sources
Categoryvfd
Supply voltage230 VAC
Frame sizeB2
Output typePWM output
Operating temp min-20 °C
Operating temp max50 °C

Quick answers

What is the IP rating of the AutomationDirect DURApulse GS11N-21P0?
IP20, per DURApulse AC Micro Drive: 230 VAC, 1hp with 1-phase input, (VFD) (PN# GS11N-21P0) | AutomationDirect (automationdirect.com).

Study notes

  • Rated 1 hp with 1-phase input; input phases 1, output phases 3.
  • Amperage rating 4.8 A; variable torque amperage rating 5 A.
  • Control mode selectable: sensorless vector control (SVC) or V/Hz.
  • RS-485 port on RJ45 connector, speeds up to 38.4k baud, Modbus RTU Slave and Modbus ASCII Slave.
  • Carrier frequency range 2–15 kHz; output frequency range 0.1–599 Hz.
  • Analog I/O: 1 input channel (0–20 mA, 4–20 mA, 0–10 VDC, 12-bit) and 1 output channel (0–10 VDC, 12-bit).
  • Discrete I/O: 5 sinking/sourcing inputs at 24 VDC and 2 outputs rated 240 VAC and 48 VDC; one Form C (SPDT) relay; load current 3 A/point relay, 50 mA/point discrete.
  • Spring clamp terminals; mounting is panel or wall; frame size B2.
  • Input signal options: 4–20 mA, voltage or potentiometer input; output type PWM; reverse capability built-in.
  • No integrated EMI filter and not internally bypassed; a user-supplied external fuse is required.
  • Item shipping weight stated as 2.85 lb.
  • Configuration software listed as GSOFT2; GS10 firmware available separately.

Safety

  • Safe Torque Off (STO): none.
  • Enclosure IP20; enclosed, panel or wall mounting.
  • Operating temperature rating -20 to +50 °C.
  • User-supplied external fuse required for protection.
  • UL Listed, file # E198015; UL Recognized and UL Hazardous files: none; CSA file: none.
  • CE declaration and RoHS status: compliant (see CE document); EU REACH document provided.
↑↓ navigate↵ openesc close