Beckhoff CX5330

The Beckhoff CX5330 is a fanless embedded PC built around an Intel Atom x6214RE dual-core processor at 1.4 GHz with 4 GB LPDDR4 RAM. It provides two Ethernet ports, four USB 3.1 ports, one DisplayPort, and an optional interface, and can run Windows IoT, TwinCAT/BSD, or Beckhoff RT Linux depending on the ordering variant. It supports TwinCAT 3 PLC and motion-control runtimes and operates from -25 to +60 °C.

Source checked9/9 values · 2026-10-25Beckhoff AutomationEmbedded PC
CX5330X1X22 × ETHERNETIntel Atom® x6214RE, 1.4 GHz24 V DC (-15%/+20%), electricaIP20CX5330 · FRONTSchematic · port count from spec
IP rating
IP20
Weight
1.195kg

Specification

1 source
Categoryembedded pc
Ethernet ports2
ProcessorIntel Atom® x6214RE, 1.4 GHz
Supply voltage24 V DC (-15%/+20%), electrically isolated
Power consumption0.016 kW
Operating temp min-25 °C
Operating temp max60 °C

Quick answers

How much does the Beckhoff CX5330 weigh?
1.195 kg, per Embedded PC with Intel Atom® x6214RE (beckhoff.com).
What is the IP rating of the Beckhoff CX5330?
IP20, per Embedded PC with Intel Atom® x6214RE (beckhoff.com).

Study notes

  • Main memory is 4 GB LPDDR4 RAM and can be expanded ex factory to 8 GB with option CX2900-0308.
  • A system module or fieldbus module from the CX2000 series can be plugged into the left-side multi-pole connection; the total number of plug-in modules is limited to one.
  • Optional interfaces include EtherCAT master/slave, PROFIBUS master/slave, CANopen master/slave, and an Ethernet switch expandable for real-time protocols such as PROFINET, EtherNet/IP, and BACnet/IP.
  • TwinCAT/BSD requires a CFast card with at least 20 GB; Windows 10 IoT Enterprise requires at least 40 GB; Windows 11 IoT Enterprise requires at least 80 GB and recommends expanding RAM to 8 GB.
  • The 1-second UPS is integrated with 1 MB on the CFast card.
  • Maximum power consumption is 16 W, or 38 W with UPS loading.
  • Storage temperature range is -40 to +85 °C; relative humidity is 95% without condensation.
  • TwinCAT 3 platform level is Performance (40).

Safety

  • CE and UL approvals are stated. ATEX, IECEx and cFMus approvals require the CX2900-0110 ordering option, which is mandatory for use in hazardous areas Zone 2/22 or Class I, Division 2.
  • With CX2900-0110, Ex marking is ATEX II 3G Ex ec IIC T4 Gc, IECEx Ex ec IIC T4 Gc, and cFMus Class I Division 2 Groups A, B, C, D / Class I Zone 2 AEx ec IIC T4 Gc.
  • Read the device documentation for use in hazardous areas carefully.
↑↓ navigate↵ openesc close